    Automatic Capacitance & Tan Delta Tester

    JXJS-10 automatic capacitance& tan delta tester has bridge, variable frequency converter, AC testtransformer and standard capacitor inside. It can be used to measure thedielectric loss on site (power plants or substations) or in the lab (loadcapacitor, capacitive voltage divider, current transformer, grading capacitors,surge arresters, shunt reactors, bushings, etc ). It has tunable frequency andanti-interference function. 

    Features

    (1) With big LCDto show the measurement data;

    (3) Automaticallyrecognize the test object whether it is capacitive, inductive or resistive,easy operation;

    (4) Can connect anexternal standard capacitor, or connect an external oil cup to measure thedielectric loss of insulation oil, or connect measuring electrodes to measurethe dielectric loss of solid insulation material.

    (5) Automaticallyrecognize 50Hz/60Hz power source;

    (6) With Series orParallel methods of measurement;

    (7) Automaticallyrecognize external HV power source with frequency between 40-70Hz, can be usedtogether with AC test transformer or AC resonant test system;

    (8) 100 test resultsstorage facility, computer interface.

    Specification


    Capacitance measurement range

    Internal power source:3pF~60nF/10kV, 60pF~1μF/0.5kV

    External power source: 3pF~1.5uF/10kV, 60pF~30uF/0.5kV

    Measuring Accuracy

    Capacitance: ±(1%* reading+2pF)

    Dielectric loss: ±(1%·*reading+0.04%)

    Minimum resolution

    Capacitance:0.001pF

    Dielectric loss:0.001%

    Test current

    5uA~5A

    Internal HV power source

    Output voltage:0.5~10kV; Resolution:1V;

    Accuracy: ±(1.5% *reading +10V)

    Maximum output current: 200mA

    Test frequency:45,50,55,60,65Hz or 45/55Hz,55/65Hz, 47.5/52.5Hz; Resolution:±0.01Hz

    External HV power source

    Maximum test current:10kV/5A, 50Hz power frequency or variable frequency 40-70Hz

    CVT LV output

    Output voltage:3~50kV; Output current: 3~30A

    Test time

    About 15 s

    Input power supply

    180~270V AC, 50/60Hz

    Environmental temperature

    -10~50℃

    Relative humidity

    less 80% RH, no condensing

    Dimension

    430mm(L)*320mm(W)*330mm (H)

    Net weight

    29kgs

    Trade Information
    • 3000 Per Month
    • 10-15 Days
      Contact Us

      Wujian Town Yangzhou Jiangsu China 86-15801788963-788963
      Phone :86-15801788963-788963